Input (DC)
DC convertible power (@cosφ=1) | 1150W |
Max. input voltage | 500V |
MPP voltage range / rated input voltage | 90-450V / 360V |
Min. start voltage | 80V |
Min. feed-in power | 10W |
Max. input current per MPPT | 12A |
Number of MPPTs | 1 |
Number of independent MPP inputs | 1 |
Output (AC)
Rated active power | 1000W |
Max. apparent AC power | 1100VA |
Nominal AC voltage / range | 220, 230, 240V / 180-280V |
AC power frequency / range | 50 / +-5Hz |
Rated power frequency / rated grid voltage | 50Hz / 230V |
Max. output current | 5.5A |
Power factor (@rated power) | 1 |
Adjustable displacement power factor | - |
Feed-in phases / connection phases | 1 / 1 |
Harmonic distortion (THD) at rated output | < 3% |
Efficiency
Max. efficiency / European weighted efficiency | 95.7% / 95% |
MPPT Efficiency | 99.5% |
Protective devices
DC isolator | ○ |
PV iso / Grid monitoring | ● / ● |
DC reverse polarity protection / AC short-circuit current capability | ● / ● |
GFCI function | ● |
Protection class (according to IEC 62103) / Overvoltage category (according to IEC 60664-1) | I / II (DC), III (AC) |
General data
Interfaces: RS485 / RS4851 & Ethernet & WIFI & a.RJ452(DRED) | ● / - |
Display | 16 x 2 characters |
Dimensions (W x H x D) | 352 x 415 x 128mm |
Weight | 11.5kg |
Cooling concept | Convection |
Noise emission (typical) | < 20 dB(A)@1m |
Installation | Indoor & Outdoor |
Mounting information | Wall mounting bracket |
DC connection technology | SUNCLIX |
AC connection technology | Plug-in |
Operating temperature range | -25℃ … +60℃ / -13℉ … +140℉ |
Relative humidity (non-condensing) | 0% ... 100% |
Max. operating altitude | 2000m |
Degree of protection (according to IEC 60529) | IP65 |
Climatic category (according to IEC 60721-3-4) | 4K4H |
Topology | Transformerless |
Self-consumption (night) | < 1W |
Standby power | 6W |
1For connection to approved smart meters in zero export installations
2Analog RJ45 interface to DRED in Australia & New Zealand
● standard
○ optional
- not available